Product Description
Product properties:
Product type: Ready to use
Freezing point: -50°C
Main substance content: propylene glycol not less than 60% by weight
Inhibitor: yes, ASTM D3306 standard
Boiling Point: (°C): 107°C
Density at 20ºC: 1.047 g/cm3
Recommended storage temperature minimum: 0 C maximum: 30 C
Country of origin: Estonia
Service life: at least 7 years and depends on operating rules
Shelf life: 36 months.
Packaging: 5 lit, 25 lit, 200 lit, 1000 lit
Article: ECO-50PRO57-55-6
EAN 4742668000089 5-lit plastic can
4742668000096 20-lit plastic can
4742668000447 200-lit plastic drum
4742668000454 1000-lit IBC container
Description:
Master ECO™ coolants for heating and heat exchange based on propylene glycol are characterized by the following positive properties:
● are environmentally friendly and non-toxic;
● Master ECO™ trademarks can withstand high temperatures;
● reliably protect the heating system from freezing at low ambient temperatures in winter;
● have lubricating and bactericidal properties;
● have good thermophysical characteristics, thanks to which the room is heated evenly;
● fire and explosion proof;
● do not form scale.
● neon dyes are used, which help to more easily detect the leak in the event of a leak in the system (the need for such an additive is indicated when ordering)
User manual:
Before using Master ECO™ coolants, the heating system must be completely cleaned of waste liquid. You should also remove old deposits and scales from the circuit, eliminate corrosion traces, and ensure there are no zinc-containing parts.
The heating system is filled by gravity, either manually or under pressure. The manual filling is applicable for open circuits. Coolant is pumped into closed heating systems under pressure using pumps.
It is important to ensure a good seal, since aqueous propylene glycol solutions, having a high wetting effect, can leak where water does not flow. If it leaks, the efficiency of the entire heating system decreases. If they are detected, it is necessary to pause the entire system’s operation and eliminate the malfunction.
Procedure in case of emergency shutdown of the heating system.
Solutions of propylene and water at zero temperatures and below have a high level of viscosity. Therefore, if the system has cooled down, it is recommended to first turn on the heating elements themselves, and then start circulation. This will reduce the load on the pumps.
The service life of Master ECO™ coolants is at least 7 years. The price of the coolant depends on the concentration of the main base component. When ordering and purchasing it, it is necessary to consider the percentage of propylene glycol in the coolant brand. The temperature range in which the all-season low-freezing coolant will be in a working condition depends on this indicator.
Master ECO-50PRO™ Thermophysical properties of 60% aqueous solution of propylene glycol, crystallization temperature minus – 50°C
Solution temperature, t°C |
Density, kg/m**3 |
Heat capacity, Average, kJ/(kg*K) |
Thermal conductivity, W/(m*K) |
Dynamic viscosity, *10-3[N*s/m**2] |
Kinematic viscosity, *10-6[(m**2/s] |
-50°C |
1071 |
Not Tested |
Not Tested |
Not Tested |
Not Tested |
-40°C |
1070 |
3.12 |
0.353 |
243.0 |
245 |
-30°C |
1069 |
3.20 |
0.354 |
195.5 |
196 |
-20°C |
1067 |
3.24 |
0.355 |
92.3 |
93 |
-10°C |
1054 |
3.27 |
0.324 |
41,2 |
42 |
0°C |
1059 |
3.30 |
0.355 |
24.3 |
25 |
20°C |
1047 |
3.36 |
0.353 |
8.2 |
9 |
40°C |
1039 |
3.44 |
0.357 |
3.87 |
4 |
60°C |
1023 |
3.51 |
0.363 |
1.886 |
1.9 |
80°C |
1017 |
3.57 |
0.364 |
1.38 |
1.4 |
100°C |
998 |
3.64 |
0.370 |
0.874 |
0.88 |
Dimensions | N/A |
---|---|
Pieejamais apjoms | 5 lit plastic can, 20 L plastic bucket/canister, 200 L (without container cost), 1000 L (without container cost) |